AERCO ProtoNode Gateway
User Manual
Page 12 of 126 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
2.4.5 S0S3 Bank DIP Switches to Select and Load Device Configuration Files
The “S” Bank of DIP switches (S0 - S3) is used to select and load a configuration file from a
group of pretested/preloaded configuration files, which are stored in the ProtoNode RER
FPC-N34 (BACnet MS/TP, BACnet/IP, Modbus TCP, Metasys N2) and the ProtoNode LER
FPC-N35 (LonWorks).
Figure 2-4: S0-S3 DIP Switch Locations
2.4.5.1 ProtoNode RER S0 to S3 (and A1& A3) DIP Switch Settings
The “A1” and “A3” switches listed in the chart below refer to the additional Mini DIP switches,
NOT the “ABank DIP switches (A0 A7) that are accessible with the cover on. To access
the Mini DIP switches you must remove the cover, as shown in Figure 2-5.
Except for those listed below, all other Mini DIP switches are in the
Off position.
TABLE 2-4: ProtoNode RER S0 to S3 (and A1*) DIP Switch Settings
S0
S1
S2
S3
A1
Profile
Off Off
Off
Off
Off
BACnet/IP/BACnet MS/TP, 1 ACS/BMS II, 4 C-More Controlled Boilers
ON
Off
Off Off Off
BACnet/IP/BACnet MS/TP, 1 ACS/BMS II, 8 C-More Controlled Boilers
Off
ON
Off Off Off
BACnet/IP/BACnet MS/TP, 1 ACS/BMS II, 12 C-More Controlled Boilers
ON
ON
Off Off Off
BACnet/IP/BACnet MS/TP, 1 ACS/BMS II, 4 Modulex Boilers With BCMs
Off
Off
ON
Off Off
BACnet/IP/BACnet MS/TP, 4 ECS/SP Systems
ON
Off
ON
Off Off
BACnet/IP/BACnet MS/TP, 12 C-More, 6 ECS/SP, 4 Modulex and 2 ACS/BMS II
Off
ON
ON
Off Off
Metasys N2, 1 ACS/BMS II, 4 C-More Controlled Boilers
ON
ON
ON
Off Off
Metasys N2, 1 ACS/BMS II, 8 C-More Controlled Boilers
Off Off Off
ON
Off
Metasys N2, 1 ACS/BMS II CS, 12 C-More Controlled Boilers
ON
Off
Off
ON
Off
Metasys N2, 1 ACS/BMS II, 4 Modulex Boilers with BCMs
Off
ON
Off
ON
Off
Metasys N2, 4 ECS/SP Systems
ON
ON
Off
ON
Off
Metasys N2, 12 C-More, 6 ECS/SP, 4 Modulex and 2 ACS/BMS II
Off
Off
ON
ON
Off
Modbus TCP, 1 ACS/BMS II, 4 C-More Controlled Boilers
ON
Off
ON
ON
Off
Modbus TCP, 1 ACS/BMS II, 8 C-More Controlled Boilers
Off
ON
ON
ON
Off
Modbus TCP, 1 ACS/BMS II, 12 C-More Controlled Boilers
ON
ON
ON
ON
Off
Modbus TCP, 1 ACS/BMS II, 4 Modulex Boilers With BCMs
Off
Off Off Off
ON
Modbus TCP, 4 ECS/SP Systems
ON
Off Off Off
ON
Modbus TCP, 12 C-More, 6 ECS/SP, 4 Modulex and 2 ACS/BMS II
S0
S1
S2
S3
A1
A3
Profile
ON
Off Off Off Off
ON
Slave/Slave Device (SSD) Modbus for WHM and BST systems
Off
ON
Off Off Off
ON
Slave/Slave Device (SSD) Bacnet for WHM and BST systems
ON
ON
Off Off Off
ON
Slave/Slave Device (SSD) N2 for WHM and BST systems
S0 – S3 DIP
Switches
S Bank DIP
Switch
Location
A Bank DIP
Switch
Location
Mini DIP
Switches
Located
Under
Cover
S0 S1 S2 S3